Noise Criteria (NC/RC) — HVAC Assessment

NC curves per ASHRAE Chapter 48 define maximum background noise in octave bands 63 Hz-8 kHz. The NC rating equals the lowest curve not exceeded. NC is the primary method for specifying and verifying HVAC noise in commercial buildings.

ASHRAE Handbook Ch. 48ANSI/ASA S12.2-2019

Structure

Octave bands 63-8 kHz, sloping down. NC-35: 62 dB at 63 Hz, 36 dB at 4 kHz. Rating = highest tangent band.

Targets

Concert halls NC-15-20. Churches NC-25-30. Offices NC-30-35. Open plan NC-35-40. Retail NC-40-45.

RC Method

Evaluates balance: average 500/1k/2k Hz, check low/high deviation. RC-N (neutral), RC-R (rumbly), RC-H (hissy). Better diagnostic than NC.

Troubleshooting

Low-freq excess: duct rumble, fan. Mid: airflow at diffusers. High: turbulence at grilles.